Zone control for air and heat on southwind 08

  • 05/27/2012 9:45 AM
    Message # 931740
    Deleted user
    We have a southwind 08 gas model. We have always had issues with zone 1 for controlling tempertures. Sometimes it would work and other times it would read 103, therefore not shutting off air on auto. Also heat would never go on due to temp not registering correct. We changed the sensor and also location of it. Also awhere of flourscent lighting. Does anyone else have this problem and how was it resolved?   
  • 05/28/2012 6:53 AM
    Reply # 932839 on 931740
    Roy Shoemaker
    I had that problem on my 02 Bounder.  Zone one is the area where the thermostst is located.  If the thermostst is located in the bedroom, then that is zone 1.  On my ubit, the wiring was wrong.  Zone 1 was actua;;y reading the temp. from Zone 2.  I reversed the wiring and it works fine.  The Zone wires are Blue and Blue/white.  I cut the wires and used but connectors to attach the blue to blue/white and the blue/white to the blue.  Now the zones reads correctly.  It corrects the heating also.
  • 06/16/2021 2:15 AM
    Reply # 10646314 on 931740
    Anonymous

    My 2018 southwind 37H, the zone controls are high above the door. I am 6'2" and have to get a step stool to set. Do any of you have the same problem?